Turbo Blowers
Turbo Blower
Aerzen Turbo Generation 5plus
Aerzen Turbo Blower Generation 5plus is an excellent choice for high-speed turbo blower. This turbo blower is ideal for volume flows between 360 and 8400 m³/h. It has a significantly smaller physical footprint but boasts up to 10% higher operational efficiency than conventional turbo blowers.
Volume flow:
211,896
to
5,532,84
CFM
Differential pressure (Δp):
2,9
to
14,5
psi
Medium:
Air
Conveying / Compression:
Oil-free
The advantages of AERZEN Turbo Generation 5plus at a glance:
- 360 to 8400 m³/h air and gas volume flow range
- Speed-controlled
- Plug-and-play design
- Up to 10% more efficient than standard turbo technology
- Extended bearing life due to high-tech AERZEN air bearings featuring double coating for maximum performance and energy efficiency
US Units
Yes- Type of technology
- Turbo Blowers
- Design
- Positive pressure
- Differential pressure (Δp)
- 2,9 to 14,5 psi
- Volume flow
- 211,896 to 5,532,84 CFM
- Medium
- Air
- Conveying / Compression
- Oil-free
Aerzen Turbo Blower Generation 5plus is another excellent choice for high-speed turbo blower. This turbo blower is ideal for volume flows between 360 and 8400 m³/h. It has a significantly smaller physical footprint but boasts up to 10% higher operational efficiency than conventional turbo blowers.
This space-saving high-speed turbo blower is 100% oil-free. It has numerous applications in water and wastewater treatment, pneumatic transport of bulk materials, and chemical and process technologies.
The key features and benefits of this high-speed turbo blower include:
- 360 to 8400 m³/h air and gas volume flow range
- 100% oil-free
- Speed-controlled
- Plug-and-play design
- Up to 10% more efficient than standard turbo technology
- Extended bearing life due to high-tech AERZEN air bearings featuring double coating for maximum performance and energy efficiency
- Minimal maintenance requirements
There's a lot to be said about the economical Turbo. We'll make it brief here.
AERZEN has built turbo blowers since 1911. Over the years, we’ve continued to perfect these assemblies from a technological standpoint. Along the way, we’ve developed expertise that sets standards worldwide today. It’s reflected in the performance characteristics, in every component, and in all the details of the newest Turbos. Discover the new Turbo Generation 5 and Generation 5plus.
100% Turbo
- For small and large volume flows
- From 300 m³/h to 16,200 m³/h
- Speed-controled
- 100% oil-free
Efficient peak values
- Increase in energy efficiency by up to 10% compared to conventional turbo technology
- Control range of 40% - 100%
- Highly efficient individual components
Innovation driver: the permanent magnet motor
- Extremely high-efficiency and energy-saving permanent magnet motor
- Requires no additional energy to magnetize the rotor
- Outstanding efficiency of an almost constant 96%, even in partial load operation
Innovative AERZEN air foil bearings
- Forward-looking double coating made of Teflon and graphite
- Theoretical bearing lifetime of >80,000 operating hours, regardless of stop and start cycles (>80 starts/stops per hour)
- Resistant to pressure peaks (for example, SBR processes, pulsations caused by positive displacement machines) and compressor surge
- Highly functional without necessary accessories (for example, electric control system, back up bearings, auxiliary electronics such as battery systems)
- Highly reliable operation even during voltage fluctuations and power supply failures
- 100% maintenance free
Further information are available within the product brochure (please select a performance to see the product brochure)
Aerzen Turbo G5plus
The powerful turbo blowers of the Aerzen Turbo series are particularly suitable for use in municipal or industrial wastewater treatment plants and cover with now 21 models a volume flow range from 300 m³/h to 16,200 m³/h and system pressures up to 1,000 mbar.
Turbo Blower
Aerzen Turbo Generation 5plus
—
Performances & dimensions
Series | Performance data | Dimensions and weights | |||||||
---|---|---|---|---|---|---|---|---|---|
Pressure difference, psi | Volume flow*, CFM | Motor power, hp | Sound pressure, max. db(A) | Width (W), in | Depth (D), in | Height (H), in | Nominal size | Weight, lb | |
AT 25-0.8 S G5plus | 11,6 | 529,74 | 33,5 | 72 | 31 | 41 | 59 | DN 100 | 1,146 |
AT 35-0.8 S G5plus | 11,6 | 706,32 | 44,3 | 72 | 31 | 41 | 59 | DN 100 | 1,213 |
AT 50-0.6 S G5plus | 8,7 | 1,589,22 | 53,6 | 72 | 31 | 41 | 59 | DN 150 | 1,653 |
AT 50-0.8 S G5plus | 11,6 | 1,118,34 | 60,3 | 72 | 31 | 41 | 59 | DN 150 | 1,213 |
AT 60-0.9 S G5plus | 13,05 | 1,559,79 | 67,1 | 73 | 31 | 41 | 59 | DN 150 | 1,323 |
AT 75-0.6 S G5plus | 8,7 | 2,295,54 | 87,2 | 73 | 35 | 45 | 63 | DN 200 | 1,653 |
AT 75-0.8 S G5plus | 11,6 | 1,706,94 | 87,2 | 73 | 35 | 45 | 63 | DN 200 | 1,653 |
AT 100-0.6 S G5plus | 8,7 | 3,001,86 | 114, | 73 | 35 | 45 | 63 | DN 250 | 1,653 |
AT 100-0.8 S G5plus | 11,6 | 2,295,54 | 114, | 73 | 35 | 45 | 63 | DN 200 | 1,653 |
AT 100-1.0 S G5plus | 14,5 | 1,765,8 | 114, | 73 | 35 | 45 | 63 | DN 200 | 1,653 |
AT 150-0.6 S G5plus | 8,7 | 4,591,08 | 160,9 | 73 | 39 | 51 | 75 | DN 250 | 1,918 |
AT 150-0.8 G5plus | 11,6 | 3,178,44 | 160,9 | 73 | 39 | 51 | 75 | DN 250 | 1,918 |
AT 150-1.0 S G5plus | 14,5 | 2,825,28 | 174,3 | 73 | 39 | 51 | 73 | DN 250 | 1,918 |
AT 200-0.8 S G5plus | 11,6 | 4,944,24 | 221,3 | 73 | 39 | 51 | 73 | DN 250 | 1,918 |
AT 200-1.0 S G5plus | 14,5 | 3,531,6 | 221,3 | 73 | 39 | 51 | 73 | DN 250 | 1,918 |
AT 250-0.9 S G5plus | 13,05 | 5,532,84 | 214,6 | 76 | 39 | 51 | 73 | DN 250 | 1,918 |
Sound pressure level without blow-off noise, with acoustic enclosure.
* corresponds to the measured delivery volume flow converted to the customer-specific suction conditions p = 1,0 bar, t =20°C, rF = 0%